b. Neither water wash nor dry filter filtration systems can reduce the
concentration of volatile organic compounds in the exhaust air stream.
Consult the environmental department for controlling volatile organic
compounds.
9-3.2
Storage and Mixing Room. Refer to the ACGIH IV Manual, Paint Mix
Storage Room, VS-75-30 for the design of ventilation system.
9-3.3
Paint Mix Hoods. Figure 9-4 is an example of a workbench and a floor
hood designed for paint mixing. Provide 0.5 m3/s per m2 (100 cfm per square foot) of
hood face.
Figure 9-4 Paint mixing hood and work bench
NOTES:
1.
Size each plenum take-off for no more than 2.44 m (8 ft) of plenum width. Size
each plenum for a maximum plenum velocity of 5.08 m/s (1,000 fpm).
2.
Perforated plate with 9.53 mm (3/8-in) holes. Size open area for an airflow
velocity of 10.16 m/s (2,000 fpm) through holes.
9-4
FANS AND MOTORS. Use explosion proof motor and electrical fixtures for
exhaust fan. Do not place electric motors, which drive exhaust fans, inside booths or
ducts. See 4-4.2 for more detailed information about fan selection.
9-5
REPLACEMENT AIR. There is no control over the room temperature or
room static pressure for non-mechanical replacement air systems. Dust from outside
9-6