MIL-HDBK-1003/3
Table 17 (Continued)
Equipment for VAV HVAC Control System XX
LOOP CONTROL
DEVICE
DEVICE
ADDITIONAL
FUNCTION
NUMBER
FUNCTION
SETPOINT
RANGE
PARAMETERS
SAFETY &
SD-XX01
SUPPLY AIR
--
--
--
MAINTENANCE
SMOKE DETECTOR
(CONT'D)
SD-XX02
RETURN AIR
--
--
--
SMOKE DETECTOR
DP-XX01
FILTER STATUS 0.5 IN.
0-2 IN.
--
DIFFERENTIAL
W.G.
W.G.
PRESSURE
50-100O F
TS-XX04
RETURN AIR
--
--
TEMPERATURE
SENSOR
SUPPLY FAN
R-XX01
SUPPLY FAN
--
--
--
CS-XX01
SUPPLY FAN
--
--
--
CURRENT SENSOR
H-70O F
50-100o F WITH
ROOM SENSORS TS-XX04
ROOM
C-76o F
(MULTIPLE)
TEMPERATURE
SETPOINT
N-55o F
SENSORS
ADJUST-
MENT &
OVERRIDE
SWITCH
DA-XX04
VAV TERMINAL
--
4-20 ma ONE PER
BOX COLD AIR
ZONE
VALVE
VLV-XX03
--
4-20 ma CV VARIES
COIL VALVE
CLOSE
AGAINST
16 PSIG
R-XX02
VAV TERMINAL --
--
--
BOX FAN START
h) Room Control Mode: A room type dry bulb
temperature sensor located in the most critical spot shall, on a
rise in dry bulb temperature in the space, gradually open the VAV
terminal box cold air valve.
8.6
8.6.1
Functional Performance Test. Participate in the
functional performance test as described in ASHRAE Guideline 1.
124