MIL-HDBK-1003/3
Table 17
Equipment for VAV HVAC Control System XX
LOOP CONTROL
DEVICE
DEVICE
ADDITIONAL
FUNCTION
NUMBER
FUNCTION
SETPOINT
RANGE
PARAMETERS
SUPPLY AIR
DA-XX01,
DAMPER
--
4-20 ma
--
TEMPERATURE
02, 03
ACTUATOR
AMU-XX01
AIR MONI-
--
--
MIN. O.A.
TORING UNIT
XXXX CFM
65O F
--
OUTDOOR AIR
--
SOFTWARE
DB HI LIMIT
POINT
55O F
o
TS-XX01
MIXED AIR
30-130 F --
LOW LIMIT
TEMPERATURE
SENSOR
VLV-XX01
PREHEAT COIL
--
4-20 ma
CV-10
VALVE
CLOSE
AGAINST
16 PSIG
55O F
40-140o F
TS-XX02
SUPPLY AIR
--
FAN DISCHARGE
TEMPERATURE
SENSOR
VLV-XX02
COOLING COIL --
4-20 ma
CV-20
VALVE
CLOSE
AGAINST
20 PSIG
SUPPLY DUCT
PS-XX01
SUPPLY DUCT 1.5 IN. 0-5 IN.
--
STATIC
STATIC
W.G.
W.G.
PRESSURE
PRESSURE
SENSOR
PS-XX02
FAN DISCHARGE 3.5 IN. 0-5 IN. --
HIGH LIMIT
W.G.
W.G.
STATIC
PRESSURE
SENSOR
SFC-XX01 SUPPLY FAN
--
4-20 ma
VARIABLE SPEED
CONTROLLER
35o F
SAFETY &
TSL-XX01 LOW
--
--
MAINTENANCE
TEMPERATURE
PROTECTION
THERMOSTAT
123