MIL-HDBK-1003/3
Table 16 (Continued)
Equipment for Multizone HVAC Control System XX
LOOP CONTROL
DEVICE
DEVICE
ADDITIONAL
FUNCTION
NUMBER
FUNCTION
SETPOINT
RANGE
PARAMETERS
COLD DECK
VLV-XX01 PREHEAT COIL
--
4-20 ma
CV-10
TEMPERATURE
VALVE
CLOSE
(CONT'D)
AGAINST
16 PSIG
55O F
o
TS-XX02
COLD DECK
40-140 F --
TEMPERATURE
SENSOR
VLV-XX02 COOLING COIL
--
4-20 ma
CV-20
VALVE
CLOSE
AGAINST
20 PSIG
180o F 40-240o F
HOT DECK
TS-XX03
HOT DECK
TEMPERATURE
TEMPERATURE
SENSOR
4-20 ma
CV-12
VALVE
CLOSE
AGAINST
16 PSIG
O
o
ROOM SENSORS
TS-XX04
ROOM
H-70 F 50-100 F WITH
C-76o F
(MULTIPLE)
TEMPERATURE
SETPOINT
o
SENSORS
N-55 F
ADJUST-
MENT &
OVERRIDE
SWITCH
DA-XX04
ZONE DAMPER
--
4-20 ma
ONE PER
ACTUATORS
ZONE
35o F
SAFETY &
TSL-XX01 LOW
--
--
MAINTENANCE
TEMPERATURE
PROTECTION
THERMOSTAT
SD-XX01 SUPPLY AIR
--
--
--
SMOKE DETECTOR
SD-XX02 RETURN AIR
--
--
--
SMOKE DETECTOR
DP-XX01 FILTER STATUS 0.5 IN. 0-2 IN. --
DIFFERENTIAL W.G.
W.G.
PRESSURE
50-100O F --
TS-XX04
RETURN AIR
--
TEMPERATURE
SENSOR
117