MIL-HDBK-1003/3
Table 15
Equipment for Single Zone HVAC Control System XX
LOOP CONTROL
DEVICE
DEVICE
ADDITIONAL
FUNCTION
NUMBER
FUNCTION SETPOINT RANGE
PARAMETERS
ROOM ZONE
DA-XX01,
DAMPER
--
4-20 ma
MIN.O.A.
TEMPERATURE
02, 03
ACTUATOR
XXXX CFM
O
--
OUTDOOR AIR 65 F
--
SOFTWARE
DB HI LIMIT
POINT
O
o
TS-XX01
MIXED AIR
55 F 30-130 F
--
LOW LIMIT
TEMPERATURE
SENSOR
VLV-XX01
PREHEAT COIL --
4-20 ma
CV-10
VALVE
CLOSE
AGAINST
16 PSIG
O
o
TS-XX02
SUPPLY AIR
55 F 40-140 F
--
VLV-XX02
4-20 ma
CV-12
VALVE
CLOSE
AGAINST
16 PSIG
VLV-XX03
COOLING COIL --
4-20 ma
CV-20
VALVE
CLOSE
AGAINST
20 PSIG
O
o
TS-XX03
ROOM ZONE
H-70 F 50-100 F WITH
TEMPERATURE C-76o F
SETPOINT
o
SENSOR
N-55 F
ADJUST-
MENT &
OVERRIDE
SWITCH
35o F
SAFETY &
TSL-XX01
LOW
--
--
MAINTENANCE
TEMPERATURE
PROTECTION
THERMOSTAT
SD-XX01
SUPPLY AIR
--
--
--
SMOKE DETECTOR
SD-XX02
RETURN AIR
--
--
--
SMOKE DETECTOR
DP-XX01
FILTER STATUS 0.5 IN. 0-2 IN.
--
DIFFERENTIAL W.G.
W.G.
PRESSURE
113