i.
Typical Details for Securing Equipment. See
Figures 10-12 and 10-13 for examples of seismic
restraints for equipment.
10-4.
Acceptance Criteria.
a.
Performance Objective 1A. The acceptance
criteria for nonstructural components in Performance
Objective 1A is conformance with the requirements
of Chapter 6 of FEMA 302, with the importance
factor, IP, equal to 1.0, and as modified by this
document.
The required seismic forces are
represented by Equation, 10-1, 10-2, and 10-3.
b.
Enhanced Performance Objective.
Performance
Objective
1A
is
the
minimum
requirement for all nonstructural components.
Buildings
that
are
designed
for
enhanced
performance
objective,
shall
identify
critical
nonstructural components that require enhanced
performance. The enhanced performance shall be
achieved by compliance with the criteria prescribed
in this chapter, with Ip selected from Paragraph 10-
1d and with SDS from Ground Motion A or B, as
appropriate.
10 31