MIL-HDBK-1003/3
Table 21
Air Conditioning Load Estimating Factors
APPLICATIONS
AIR CONDITIONING FLOOR AREA SQ. FT./TON
(EXCEPT WHERE NOTED)
ADMINISTRATION BUILDING
450-600
AUDITORIUMS, THEATERS
0.004 TO 0.08 TONS/SEAT
BOWLING ALLEYS
0.8 TO 1.4 TONS/ALLEY
COMPUTER ROOMS
50 TO 150
DINING ROOMS
175 TO 450
DISPENSARIES
450 TO 550
ENLISTED MEN'S AND
275 TO 375
OFFICER'S CLUBS
HOSPITAL PATIENT ROOMS
450 TO 550
MULTIPLE FAMILY HOUSING
900 TO 1275
UNITS
RECREATION ROOMS
375 TO 450
RELIGIOUS FACILITIES
0.02 TO 0.03 TONS/SEATS
HOPS (PRECISION
450 TO 550
EQUIPMENT)
TRAINING FACILITIES
400 TO 500
725 TO 900
Table 22
Typical Load Breakdown of Dehumidified Warehouse
MOISTURE
MOISTURE LOAD
PERCENT OF TOTAL MOISTURE
SOURCE
LB. WATER/DAY
LOAD (FLOOR W/MEMBRANE)
FLOOR (WITHOUT
180 TO 420
----
A MEMBRANE)
FLOOR (WITH A
120 TO 240
19
MEMBRANE)
WALL TRANSMISSION
50
TO
100
8
ROOF TRANSMISSION
20
TO
60
3 TO 5
BREATHING
40
TO
55
3 TO 4
WALL INFILTRATION
150
TO
300
24
OPEN DOOR
200
TO
400
32
STORES (5% ANNUAL
50
TO
130
8 TO 11
TURNOVER)
145