Refer to 29 CFR 1910.94, .106, .107, and .108 for ventilation
requirements related to specific operations, e.g., abrasive
blasting, painting, buffing and grinding, dip tanks, and chemical
storage.
3.13
Hospital, Dental, and Medical Facilities. Military
Standard (MIL-STD)-1691, Construction and Material Schedule for
Military Medical and Dental Facilities provides utility
requirements for medical equipment to assist in determining heat
gains, ventilation requirements (e.g., fume hood exhaust), and
steam connections (e.g., sterilizers).
3.14
Family Housing. Provide access for maintenance of
mechanical equipment and devices. For safety, protect mechanical
spaces and equipment with strong door catches or shielding from
moving parts and controls. Provide ducted exhaust fans with
backdraft dampers for kitchens and interior bathrooms. Size
bathroom fans for 10 air changes per hour minimum; kitchen
exhaust fans for 15 air changes per hour minimum or 50 cubic feet
per minute per linear foot of range hood. Refer to
MIL-HDBK-1035, Family Housing for requirements on attic exhaust
fans, evaporative cooling, and air conditioning.
3.15
Bachelor Enlisted Quarters. Refer to MIL-HDBK-1036,
loads, equipment sizing, and design recommendations; except that
ventilation requirements shall be in accordance with ASHRAE
Standard 62.