(3) Masonry construction prescribed by this
failure to collapse. All connectors for load-bearing
document shall be in accordance with the following
and
non-load-bearing
walls
will
therefore
be
provisions:
designed in accordance with ACI 318, as modified by
Section 9.1.1 of FEMA 302. The shear force will be
(a) Seismic Design Categories A, B, and C.
uniformly distributed throughout the height or length
Masonry shear walls shall comply with the
of the shear wall with reasonably spaced connectors
requirements of intermediate reinforced masonry
(maximum spacing 4 feet), rather than with a few that
shear walls (Section 11.11.4 of FEMA 302) or
will have localized concentration of stresses.
special reinforced masonry shear walls (Section
Detailed calculations will be made, including the
11.11.5 of FEMA 302).
localized effects in concrete walls attributed from
these connectors. Sufficient details of connectors and
(b) Seismic Design Categories D, E, and F.
embedded anchorage will be provided to preclude
Masonry shear walls shall comply with the
construction deficiency.
requirements of special reinforced masonry shear
walls (Section 11.11.5 of FEMA 302).
(4) Typical details. Refer to Figure 7-9 for
details.
(c) Basic requirements. Unit masonry will
be reinforced with deformed bars for axial, flexural,
(5) Acceptance criteria. FEMA 302 requires
shear, and diagonal tension stresses as determined by
that connections for precast concrete walls shall be
design calculations. Additional reinforcing bars are
designed to be stronger than the adjacent precast
prescribed for use around openings, at corners, at
panels.
The lateral-load response behavior is
anchored intersections, and at the ends of wall panels
therefore comparable to that for monolithic shear
(for example, at control joints).
The minimum
walls, and the acceptance criteria of Paragraph 7-
reinforcement prescribed in FEMA 302 is intended to
2f(3) will be applicable.
provide empirical requirements relative to damage
h.
Masonry Shear Walls.
control (ductility and boundary conditions). Layout
and details of construction will be compatible with
the application of the rules for modular measure.
(1)
General design criteria.
This section
prescribes the criteria for the structural design of
(d)
Types of reinforced masonry walls.
shear walls of unit masonry construction. The basic
Masonry will conform to one of the following basic
reference documents are FEMA 302 and ACI 530.
types: reinforced grouted masonry, reinforced hollow
masonry, or reinforced filled-cell masonry.
(2)
Unreinforced or plain masonry bearing
walls or shear walls, where permitted, shall be used
only for buildings in Seismic Design Category A or
B. Design shall be in accordance with Section 11.3.3
of FEMA 302.
7-28