UFC 3-240-13FN
25 May 2005
also serves to protect feedwater piping from corrosion. A sufficient amount of the
oxygen scavenger must be fed to meet the demand for the oxygen initially present and
provide an excess residual (reserve amount) for occasions when the oxygen level may
increase unexpectedly, so that water testing will always indicate that an excess amount
is present. (See Table 3-3 for typical sulfite levels in the boiler water.)
Table 3-3. Levels of Sulfite to be Carried in Boiler Water
Sulfite
Boiler Pressure
Residual
KPa (psig)
(as ppm SO3)
0-103 (0-15)
20-40
110-1020 (16-149)
20-40
1030-2060 (150-299)
20-40
2070-3100 (300-449)
20-40
3100-4130 (450-599)
20-40
4140-5160 (600-749)
15-30
> 5170 (> 750)
15-30
3-2.6.2.2
Oxygen Scavengers for Boilers Over 6205 Kilopascals.
For boilers
over 6205 kilopascals (900 pounds per square inch gauge), the list of oxygen
scavengers includes specialty volatile treatments such as hydroxylamine, hydroquinone,
carbohydrazide, hydrazine sulfate, and erythorbic acid. Hydrazine can no longer be
used because it is a suspected carcinogen. Like hydrazine, these specialty volatile
treatments not only scavenge oxygen but also passivate metal surfaces. These
chemicals are normally maintained in the boiler water in the parts-per-billion (ppb)
range. Sulfite-type oxygen scavengers are not used in boilers over 6205 kilopascals
(900 pounds per square inch gauge) because of the potential for thermal decomposition
producing sulfur dioxide and hydrogen sulfide, both of which can cause corrosion. The
thermal decomposition reactions are:
Na2SO3 + H20 + Heat → 2NaOH + SO2↑
EQUATION
(16)
4Na2SO3 + 2H2O + Heat → 3Na2SO4 + 2NaOH + H2S↑
EQUATION
(17)
These reactions have been shown to occur at boiler pressures as low as 4140
kilopascals (600 pounds per square inch gauge), although they do not usually create a
serious problem until pressures exceed 6205 kilopascals (900 pounds per square inch
gauge).
58