q. Each LAN workstation signed will be provided with an additional well-defined
adjacent duplex receptacle on an independent single phase (20 ampere, 120 volt) circuit
having not more than four duplex receptacles and a nonshared neutral. Where a 20 ampere,
120 volt receptacle is incorporated in the same metal box with a television, or LAN outlet, a
partitioned metal box with separate power and signal conduits will be provided.
r. Provide independent circuits for FAX and copy equipment and laser printers and
coordinate the location with the customers.
s. Discuss any requirements for connection to the installation electronic security system.
t. If interfacing with existing electronic security systems is required, describe these
existing systems in the RFP technical specifications.
u. Consider a requirement to design electronic security systems for future expansion.