CEMP-E
TI 810-11
30 November 1998
HARDWARE
SOFTWARE
OUTPUT
INPUT
ALARMS
APPLICATION
PROGRAMS
DIGITAL
ANALOG
DIGITAL
ANALOG
DIGITAL
ANALOG
SUPPLY FAN
1
1
X
X
X
X
X
X
SPACE
1
X
X
X
X
MIXED AIR DAMPERS
1
1
COOLING COIL VALVE
1
SMOKE DETECTOR
2
X
FREEZESTAT
1
X
1
FILTER
X
**
C - LAST COMMAND
O - ON (OPEN)
H - HIGH VALUE
F - OFF (CLOSED)
L - LOW VALUE
DDC DATA TERMINAL STRIP LAYOUT
DEVICE NO.
TYPE
DESCRIPTION
1
2
3
TT-XX-01
SPACE TEMPERATURE
AI
4
5
IP-XX-01
MIXED AIR DAMPERS
AO
6
IP-XX-02
AO
7
IP-XX-03
COOLING COIL VALVE
AO
8
9
10
SMK-XX-01
SUPPLY AIR SMOKE DETECTOR
DI
11
SMK-XX-02
RETURN AIR SMOKE DETECTOR
DI
12
TSL-XX-01
FREEZESTAT
DI
13
DPS-XX-01
FILTER ALARM
DI
14
15
C-XX-04
SUPPLY FAN START/STOP
DO
16
C-XX-05
SUPPLY FAN STATUS
DI
17
18
19
20
Figure 5-15j. DDC control system I/O table and data terminal strip layout for single-zone HVAC system
without economizer control mode.