CEMP-E
TI 810-11
30 November 1998
TuP
LOC: PER SCHEDULE
XX-01
SUPPLY
RETURN
NO
VLV
FTR
XX-01
SCHEMATIC VARIATION FOR UNOCCUPIED-MODE SETBACK
H OR X
N OR X
2
1
LOC: PER
TuP
SCHEDULE
XX-01
VLV
XX-01
NO
LADDER-DIAGRAM VARIATION FOR UNOCCUPIED-MODE SETBACK
SPACE
FTR
THERMOSTAT
VALVE
REMARKS
XXXX
XX
TuP-XX-01
VLV-XX-01
Kv=.17 (Cv=0.2)
CLOSE AGAINST 70 kPa (10 PSIG)
SET: DAY = 20 DEG C (68 DEG F)
NIGHT = 13 DEG C (55 DEG F)
YYYY
TuP-XX-XX
YY
VLV-XX-XX
Kv=.60 (Cv=0.7)
CLOSE AGAINST 70 kPa (10 PSIG)
SET: DAY = 20 DEG C (68 DEG F)
NIGHT = 13 DEG C (55 DEG F)
EQUIPMENT SCHEDULE
Figure 5-9. Control system variations for unoccupied mode setback.