CEMP-E
TI 810-11
30 November 1998
LOOP CONTROL FUNCTION
RANGE
ADDITIONAL PARAMETERS
DEVICEFUNCTION
SETPOINT
DEVICENUMBER
DA-XX-01
MIXED AIR
DA-XX-02
DAMPER ACTUATOR
21-103 kPa (3-15 PSIG)
TEMPERATURE
DA-XX-03
MIXED AIR TEMPERATURE
4 TO 60 DEG C
TC-XX-01
13 DEG C (55 DEG F)
CONTROLLER
(40 TO 140 DEG F)
MIXED AIR TEMPERATURE
4 TO 60 DEG C
TT-XX-01
TRANSMITTER
(40 TO 140 DEG F)
OUTSIDE AIR TEMPERATURE
-34 TO 54 DEG C
TT-XX-02
TRANSMITTER
(-30 TO 130 DEG F)
RETURN AIR TEMPERATURE
-34 TO 54 DEG C
TT-XX-03
TRANSMITTER
(-30 TO 130 DEG F)
PV CONTACT
DEV CONTACT
-34 TO 54 DEG C
EC-XX-01
ECONOMIZER CONTROLLER
CLOSE AT __ DEG C (__ DEG F)
CLOSE @ DELTA T= __ DEG C (__ DEG F)
(-30 TO 130 DEG F)
OPEN AT __ DEG C (__ DEG F)
OPEN @ DELTA T= __ DEG C (__ DEG F)
LOW TEMPERATURE PROTECTION
TSL-XX-01
2 DEG C (35 DEG F)
THERMOSTAT
PER FILTER
PER FILTER
MANUFACTURER'S
DPS-XX-01
FILTER ALARM
MANUFACTURER'S
RECOMMENDATION
RECOMMENDATION
MIN. OUTSIDE AIR FLOW
DA-XX-04
DAMPER ACTUATOR
21 - 103 kPa (3-15 PSIG)
MIN. OUTSIDE AIR DUCT
0 - ___ L/s
FC-XX-02
(SEE NOTE 1)
Min OA = __ L/s ( __ cfm)
FLOW CONTROLLER
(0 - ___ CFM)
UPPER RANGE AS REQUIRED
MIN. OUTSIDE AIR DUCT
0 - ___ m/s
FT-XX-03
FLOW TRANSMITTER
(0 - ___ FPM)
(SEE SPECIFICATIONS)
PER FILTER
PER FILTER
DPS-XX-03
PRE-FILTER ALARM
MANUFACTURER'S
MANUFACTURER'S
RECOMMENDATION
RECOMMENDATION
NIGHT STAT - SPACE LOW
DIFFERENTIAL =
SPACE LOW TEMPERATURE
TSL-XX-02
13 DEG C (55 DEG F)
TEMPERATURE PROTECTION
3 DEG C (5 DEG F)
Kv = __ ( Cv = __ )
DISCHARGE AIR
VLV-XX-01
COOLING COIL VALVE
21-103 kPa (3-15 PSIG)
TEMPERATURE
CLOSE AGAINST __ kPa ( __ PSIG )
FAN DISCHARGE TEMPERATURE
4 TO 60 DEG C
TC-XX-02
13 DEG C (55 DEG F)
CONTROLLER
(40 TO 140 DEG F)
FAN DISCHARGE TEMPERATURE
4 TO 60 DEG C
TT-XX-04
TRANSMITTER
(40 TO 140 DEG F)
SUPPLY DUCT
SUPPLY DUCT STATIC PRESSURE
0 - 500 kPa
PC-XX-01
300 kPa (1.2 INCHES WATER)
STATIC PRESSURE
CONTROLLER
(0.0 - 2.0 INCHES WATER)
SUPPLY DUCT STATIC PRESSURE
0 - 500 kPa
DPT-XX-01
TRANSMITTER
(0.0 - 2.0 INCHES WATER)
SUPPLY DUCT - HIGH STATIC
1000 - 1500 kPa
DPS-XX-02
PRESSURE SAFETY
(4.0 - 6.0 INCHES WATER)
RETURN FAN
RETURN FAN VOLUME
SUPPLY FAN L/s (CFM)
0 - 9500 L/s
FC-XX-01
VOLUME
CONTROLLER
MINUS ___ L/S (___ CFM)
(0 - 20,000 CFM)
SUPPLY DUCT FLOW
0 - 9500 L/s
FT-XX-01
TRANSMITTER (FPM)
(0 - 20,000 CFM)
RETURN DUCT FLOW
0 - 9500 L/s
FT-XX-02
TRANSMITTER (FPM)
(0 - 20,000 CFM)
NORMAL SCHEDULE (M-F)
OCCUPIED
CLK-XX-01
365 DAY SCHEDULE
CONTACT CLOSED: 0705 HRS
CONTACT OPEN: SAT, SUN
MODE
CONTACT
CONTACT OPEN: 1700 HRS
NORMAL SCHEDULE (M-F)
VENTILATION DELAY
CLK-XX-01
CONTACT CLOSED: 0700 HRS
365 DAY SCHEDULE
MODE
CONTACT
CONTACT OPEN: 0800 HRS
Kv = __ ( Cv = __ )
TERMINAL
VLV-XX-AA
UNITS
SPACE AA
CLOSE AGAINST __ kPa ( __ PSIG )
Kv = __ ( Cv = __ )
VLV-XX-ZZ
SPACE ZZ
CLOSE AGAINST __ kPa ( __ PSIG )
NOTES:
1. Upper range (L/s) of flow controller (FC-XX-XX) = Upper range (m/s) of associated flow transmitter (FT-XX-XX) TIMES the duct area (sq m) TIMES 1000 (L/cu. m).
(Upper range (CFM) of flow controller (FC-XX-XX) = Upper range (fpm) of associated flow transmitter (FT-XX-XX) TIMES the duct area (sq ft).
2. OTHER CONTROL DEVICES SUCH AS I/Ps, RELAYS, SIGNAL SELECTERS AND TERMINAL UNIT CONTROLLERS ARE NOT SHOWN.
Figure 5-7c. Equipment variations for variable speed drives.