CEMP-E
TI 810-11
30 November 1998
SENSOR SCHEDULE
IDENTIFIER
FUNCTION
RANGE
OUTSIDE AIR TEMPERATURE
-34 TO 54 DEG C
TT-XX-01
TRANSMITTER
(-30 TO +130 DEG F)
SPACE TEMPERATURE
10 TO 30 DEG C
TT-XX-02
TRANSMITTER
(50 TO 85 DEG F)
HEATING SUPPLY WATER
38 TO 121 DEG C
TT-XX-03
(100 TO 250 DEG F)
SUPPLY AIR RELATIVE
RHT-XX-01
0 TO 100% R.H.
RHT-XX-02
0 TO 100% R.H.
TRANSMITTER
CONTROL VALVE SCHEDULE
IDENTIFIER
FUNCTION
TYPE
RANGE
CLOSE-OFF RATING
REMARKS
Kv (Cv)
21 - 103 kPa
XX kPa
VLV-XX-01
PREHEAT COIL VALVE
2-WAY, MODULATING
XX
(3-15 PSIG)
(XX PSIG)
21 - 103 kPa
XX kPa
VLV-XX-02
COOLING COIL VALVE
2-WAY, MODULATING
XX
(3-15 PSIG)
(XX PSIG)
21 - 103 kPa
XX kPa
VLV-XX-03
2-WAY, MODULATING
XX
(3-15 PSIG)
(XX PSIG)
21 - 103 kPa
XX kPa
VLV-XX-04
HUMIDIFIER VALVE
2-WAY, MODULATING
XX
(3-15 PSIG)
(XX PSIG)
21 - 103 kPa
XX kPa
VLV-XX-05
CONVERTER VALVE
2-WAY, MODULATING
XX
(3-15 PSIG)
(XX PSIG)
CONTROL DAMPER SCHEDULE
IDENTIFIER
FUNCTION
TYPE
RANGE
REMARKS
SIZE
W x H (mm)
AD-XX-01
OUTSIDE AIR
TWO-POSITION
PARALLEL BLADE
(WW" X HH")
OPERATING PARAMETERS
FUNCTION
REMARKS
SETPOINT
XX DEG C
PREHEAT COIL DISCHARGE
(XX DEG F)
XX DEG C (XX DEG F)
(HEATING)
SPACE TEMPERATURE
XX DEG C (XX DEG F)
(COOLING)
XX DEG C
SPACE TEMP. (NIGHT SETBACK)
(HEATING ONLY)
(XX DEG F)
XX DEG C
FREEZESTAT
(XX DEG F)
SUPPLY AIR HUMIDITY
XX% R.H.
HIGH LIMIT
SPACE HUMIDITY
XX% R.H.
XX DEG C
(XX DEG F)
OCCUPIED MODE
MONDAY - FRIDAY : 0705 HRS - 1700 HRS
VENT DELAY MODE
MONDAY - FRIDAY : 0700 HRS - 0800 HRS
XX kPa
FILTER ALARM
(XX IN. WATER)
Figure 4-21i. DDC control system equipment for single zone HVAC system with humidity control.