CEMP-E
TI 810-11
30 November 1998
SOFTWARE
HARDWARE
OUTPUT
INPUT
ALARMS
APPLICATION
PROGRAMS
DIGITAL
ANALOG
DIGITAL
ANALOG
DIGITAL
ANALOG
SUPPLY FAN
1
1
X
X
X
X
X
X
SUPPLY FAN INLET VANES
1
SUPPLY AIR
1
1
X
X
RETURN AIR
1
X
X
MIXED AIR
1
X
X
MINIMUM OUTSIDE AIR
1
1
1
X
X
MIXED AIR DAMPERS
1
X
X
COOLING COIL VALVE
1
FILTER
2
X
FREEZESTAT
1
X
SMOKE DETECTOR
2
X
SUPPLY AIR HIGH STATIC
1
X
SPACE TEMP (NIGHT LOW LIMIT)
X
X
X
X
**
C - LAST COMMAND
O - ON (OPEN)
H - HIGH VALUE
F - OFF (CLOSED)
L - LOW VALUE
DDC DATA TERMINAL STRIP LAYOUT
TYPE
DEVICE NO.
DESCRIPTION
1
TT-XX-01
MIXED AIR TEMPERATURE
AI
2
TT-XX-02
OUTSIDE AIR TEMPERATURE
AI
3
TT-XX-03
RETURN AIR TEMPERATURE
AI
4
TT-XX-04
SUPPLY AIR TEMPERATURE
AI
5
TT-XX-05
SPACE TEMP (NITE LOW LIMIT)
AI
6
7
DPT-XX-01
SUPPLY AIR STATIC PRESSURE
AI
8
FT-XX-01
MINIMUM OUTSIDE AIR FLOW
AI
9
10
11
DPS-XX-01
FILTER ALARM
DI
12
DPS-XX-03
PRE-FILTER ALARM
DI
13
IP-XX-01
MIXED AIR DAMPERS
AO
14
IP-XX-02
COOLING COIL VALVE
AO
15
IP-XX-03
SUPPLY FAN INLET VANES
AO
16
IP-XX-04
MINIMUM OUTSIDE AIR DAMPER
AO
17
18
TSL-XX-01
FREEZESTAT
DI
19
DPS-XX-02
SUPPLY AIR HIGH STATIC
DI
20
SMK-XX-01
SUPPLY AIR SMOKE DETECTOR
DI
21
SMK-XX-02
RETURN AIR SMOKE DETECTOR
DI
22
23
C-XX-05
SUPPLY FAN START/STOP
DO
24
C-XX-06
SUPPLY FAN STATUS
DI
25
26
27
28
29
30
Figure 4-17j. DDC control system I/O table and data terminal strip layout for VAV HVAC system without
return fan.