CEMP-E
TI 810-11
30 November 1998
LOOP CONTROL FUNCTION
RANGE
ADDITIONAL PARAMETERS
DEVICE FUNCTION
SETPOINT
DEVICE NUMBER
DA-XX-01
MIXED AIR
DA-XX-02
DAMPERACTUATOR
21-103 kPa (3-15 PSIG)
TEMPERATURE
DA-XX-03
4 TO 60 DEG C
MIXED AIR TEMPERATURE
TC-XX-01
13 DEG C (55 DEG F)
(40 TO 140 DEG F)
CONTROLLER
4 TO 60 DEG C
MIXED AIR TEMPERATURE
TT-XX-01
(40 TO 140 DEG F)
-34 TO 54 DEG C
OUTSIDE AIR TEMPERATURE
TT-XX-02
(-30 TO 130 DEG F)
RETURN AIR TEMPERATURE
-34 TO 54 DEG C
TT-XX-03
(-30 TO 130 DEG F)
PV CONTACT
DEV CONTACT
-34 TO 54 DEG C
EC-XX-01
ECONOMIZER CONTROLLER
CLOSE AT __ DEG C (__ DEG F)
CLOSE @ DELTA T= __ DEG C (__ DEG F)
(-30 TO 130 DEG F)
OPEN AT __ DEG C (__ DEG F)
OPEN @ DELTA T= __ DEG C (__ DEG F)
LOW TEMPERATURE PROTECTION
TSL-XX-01
2 DEG C (35 DEG F)
THERMOSTAT
PER FILTER
PER FILTER
MANUFACTURER'S
DPS-XX-01
FILTERALARM
MANUFACTURER'S
RECOMMENDATION
RECOMMENDATION
MIN. OUTSIDE AIR FLOW
DA-XX-04
DAMPERACTUATOR
21 - 103 kPa (3-15 PSIG)
0 - ___ L/s
MIN. OUTSIDE AIR DUCT
FC-XX-01
(SEE NOTE 1)
Min OA = __ L/s ( __ cfm)
(0 - ___ CFM)
FLOW CONTROLLER
UPPER RANGE AS REQUIRED
0 - ___ m/s
MIN. OUTSIDE AIR DUCT
FT-XX-01
(0 - ___ FPM)
(SEE SPECIFICATIONS)
PER FILTER
PER FILTER
DPS-XX-03
PRE-FILTERALARM
MANUFACTURER'S
MANUFACTURER'S
RECOMMENDATION
RECOMMENDATION
DIFFERENTIAL =
NIGHT STAT - SPACE LOW
SPACE LOW TEMPERATURE
TSL-XX-02
13 DEG C (55 DEG F)
3 DEG C (5 DEG F)
TEMPERATURE PROTECTION
Kv = __ ( Cv = __ )
DISCHARGE AIR
VLV-XX-01
COOLING COIL VALVE
21-103 kPa (3-15 PSIG)
TEMPERATURE
CLOSE AGAINST __ kPa ( __ PSIG )
4 TO 60 DEG C
FAN DISCHARGE TEMPERATURE
TC-XX-02
13 DEG C (55 DEG F)
(40 TO 140 DEG F)
CONTROLLER
4 TO 60 DEG C
FAN DISCHARGE TEMPERATURE
TT-XX-04
(40 TO 140 DEG F)
SUPPLY DUCT
SUPPLY FAN
DA-XX-05
21 - 103 kPa (3-15 PSIG)
STATIC PRESSURE
INLETVANEACTUATOR
0 - 500 kPa
SUPPLY DUCT STATIC PRESSURE
PC-XX-01
300 kPa (1.2 INCHES WATER)
(0.0 - 2.0 INCHES WATER)
CONTROLLER
0 - 500 kPa
SUPPLY DUCT STATIC PRESSURE
DPT-XX-01
(0.0 - 2.0 INCHES WATER)
1000 - 1500 kPa
SUPPLY DUCT - HIGH STATIC
DPS-XX-02
(4.0 - 6.0 INCHES WATER)
PRESSURE SAFETY
NORMAL SCHEDULE (M-F)
OCCUPIED
CLK-XX-01
365 DAY SCHEDULE
CONTACT CLOSED: 0705 HRS
CONTACT OPEN: SAT, SUN
MODE
CONTACT
CONTACT OPEN: 1700 HRS
NORMAL SCHEDULE (M-F)
VENTILATION DELAY
CLK-XX-01
CONTACT CLOSED: 0700 HRS
365 DAY SCHEDULE
MODE
CONTACT
CONTACT OPEN: 0800 HRS
Kv = __ ( Cv = __ )
TERMINAL
VLV-XX-AA
UNITS
SPACE AA
CLOSE AGAINST __ kPa ( __ PSIG )
Kv = __ ( Cv = __ )
VLV-XX-ZZ
SPACE ZZ
CLOSE AGAINST __ kPa ( __ PSIG )
NOTES:
1. Upper range (L/s) of flow controller (FC-XX-XX) = Upper range (m/s) of associated flow transmitt er (FT-XX-XX) TIMES the duct area (sq m) TIMES 1000 (L/cu. m).
(Upper range (CFM) of flow controller (FC-XX-XX) = Upper range (fpm) of associated flow transmitte r (FT-XX-XX) TIMES the duct area (sq ft).
2. OTHER CONTROL DEVICES SUCH AS I/Ps, RELAYS, SIGNAL SELECTERS AND TERMINAL UNIT CONTROLLERS ARE T SHOWN.
ON
Figure 4-17c. Control system equipment for VAV HVAC system without return fan.