CEMP-E
TI 810-11
30 November 1998
HARDWARE
SOFTWARE
OUTPUT
INPUT
ALARMS
APPLICATION
PROGRAMS
DIGITAL
ANALOG
DIGITAL
ANALOG
DIGITAL
ANALOG
SUPPLY FAN
1
1
X
X
X
X
X
X
RETURN FAN
1
1
X
X
X
X
X
X
MIXED AIR
1
X
X
OUTSIDE AIR
1
X
X
1
RETURN AIR
X
X
COLD DECK
1
X
X
1
X
HOT DECK
X
X
MIXED AIR DAMPERS
1
X
X
COOLING COIL VALVE
1
1
FILTER
1
X
1
FREEZESTAT
X
SMOKE DETECTOR
2
X
X
X
X
SPACE TEMP
X
ZONE DAMPER
X
**
C - LAST COMMAND
O - ON (OPEN)
H - HIGH VALUE
F - OFF (CLOSED)
L - LOW VALUE
DATA TERMINAL STRIP LAYOUT
DEVICE NO.
TYPE
DESCRIPTION
1
TT-XX-01
MIXED AIR TEMPERATURE
AI
2
TT-XX-02
OUTSIDE AIR TEMPERATURE
AI
3
TT-XX-03
RETURN AIR TEMPERATURE
AI
4
TT-XX-04
COLD DECK TEMPERATURE
AI
5
TT-XX-05
HOT DECK TEMPERATURE
AI
6
7
IP-XX-01
MIXED AIR DAMPERS
AO
8
IP-XX-02
COOLING COIL VALVE
AO
9
IP-XX-03
AO
10
11
DPS-XX-01
FILTER ALARM
DI
12
TSL-XX-01
FREEZESTAT
DI
13
SMK-XX-01
SUPPLY AIR SMOKE DETECTOR
DI
14
SMK-XX-02
RETURN AIR SMOKE DETECTOR
DI
15
16
C-XX-04
SUPPLY FAN START/STOP
DO
17
C-XX-05
SUPPLY FAN STATUS
DI
18
C-XX-06
RETURN FAN STATUS
DI
19
20
TT-XX-AA
SPACE TEMP - ZONE AA
AI
21
DA-XX-AA
ZONE DAMPER - ZONE AA
AO
22
TT-XX-BB
SPACE TEMP - ZONE BB
AI
23
DA-XX-BB
ZONE DAMPER - ZONE BB
AO
24
TT-XX-CC
SPACE TEMP - ZONE CC
AI
25
DA-XX-CC
ZONE DAMPER - ZONE CC
AO
26
27
28
29
30
Figure 4-14j. DDC control system I/O table and data terminal strip layout for multizone HVAC system.