CEMP-E
TI 810-11
30 November 1998
HARDWARE
SOFTWARE
OUTPUT
INPUT
ALARMS
APPLICATION
PROGRAMS
DIGITAL
ANALOG
DIGITAL
ANALOG
DIGITAL
ANALOG
SPACE TEMPERATURE
1
X
X
X
MIXED AIR DAMPERS
1
X
X
1
HEATING COIL VALVE
SUPPLY FAN
1
1
X
X
X
X
X
X
FILTER
1
X
FREEZESTAT
1
X
SMOKE DETECTOR
2
X
**
C - LAST COMMAND
O - ON (OPEN)
H - HIGH VALUE
F - OFF (CLOSED)
L - LOW VALUE
DATA TERMINAL STRIP LAYOUT
DEVICE NO.
TYPE
DESCRIPTION
1
TT-22-01
SPACE TEMPERATURE
AI
2
IP-22-01
MIXED AIR DAMPERS
AO
3
IP-22-02
AO
4
5
6
SMK-22-01
SUPPLY AIR SMOKE DETECTOR
DI
7
SMK-22-02
RETURN AIR SMOKE DETECTOR
DI
8
DPS-22-01
FILTER ALARM
DI
9
TSL-22-01
FREEZESTAT
DI
10
11
C-XX-04
SUPPLY FAN START/STOP
DO
12
C-XX-05
SUPPLY FAN STATUS
DI
13
14
15
16
17
18
19
20
Figure 4-13j. DDC control system I/O table and data terminal strip layout for heating and ventilating system.