CEMP-E
TI 810-11
30 November 1998
SOFTWARE
HARDWARE
ALARMS
OUTPUT
INPUT
APPLICATION
PROGRAMS
DIGITAL
ANALOG
DIGITAL
ANALOG
DIGITAL
ANALOG
1
X
X
OUTSIDE AIR
X
PRIMARY SYSTEM HW SUPPLY
1
X
X
1
ZONE
X
X
ZONE
1
X
X
X
CONVERTER VALVE
1
ZONE VALVE
1
ZONE VALVE
1
PRIMARY PUMP
1
1
X
X
X
X
X
X
ZONE PUMP
1
1
X
X
X
X
X
X
1
ZONE PUMP
1
X
X
X
X
X
X
**
C - LAST COMMAND
O - ON (OPEN)
H - HIGH VALUE
F - OFF (CLOSED)
L - LOW VALUE
DDC DATA TERMINAL STRIP LAYOUT
TYPE
DEVICE NO.
DESCRIPTION
1
TT-XX-01
OUTSIDE AIR TEMPERATURE
AI
TT-XX-02
PRIMARY SYSTEM SUPPLY TEMP.
AI
2
3
IP-XX-01
CONVERTER VALVE
AO
4
5
TT-XX-03
SPACE TEMPERATURE
AI
6
7
IP-XX-02
ZONE VALVE
AO
8
9
TT-XX-04
SPACE TEMPERATURE
AI
10
11
IP-XX-03
ZONE VALVE
AO
12
13
14
15
16
C-XX-01
PRIMARY PUMP START/STOP
DO
17
C-XX-02
PRIMARY PUMP STATUS
DI
18
19
C-XX-03
ZONE PUMP START/STOP
DO
20
C-XX-04
ZONE PUMP STATUS
DI
21
22
C-XX-05
ZONE PUMP START/STOP
DO
23
C-XX-06
ZONE PUMP STATUS
DI
24
25
26
27
28
29
30
Figure 4-9j. DDC control system I/O table and data terminal strip layout for central plant high-temperature