MIL-HDBK-1133
Table 18
Commercial and Industrial Potable Water Requirements
Gallons Per Capita Per Day
Use
Unit
Minimum
Average
Maximum
Requirement
Requirement
Requirement
Air
conditioning:
recirculating
gpm/ton
-
0.05
0.10
non-
circulating
gpm/ton
-
2.50
4.00
Cooling -
diesel
engines:
recirculating
gpm/bhp
-
0.01
0.02
non-
circulating
gpm/bhp
0.25
0.33
0.40
Cooling -
steam power
gpm/bhp
1.30
0.80
1.70
plants,
recirculating
Swimming
pools:
Indoor
gal/gal
0.006
0.04
0.10
Outdoor
gal/gal
0.04
0.15
0.25
Vehicle
Washing:
Cars
gal per
-
50
-
Trucks
vehicle
-
100
-
Buses
washed
-
250
-
Irrigation:
Small lots
gpd/100
16
24
32
Large areas
sq. ft.
7,000
11,000
14,000
gpad
Laundries
gal/lb
3
4.5
6
Restaurants
gal/meal
0.5
2.0
4.0
4.1.3
aboard ship varies according to climate, the number of personnel
on board, and the class of ship. Ship's characteristics database
(SHIPS) at http://www.efdlant.navfac.navy.mil/LANTOPS_15/home.htm and CCB contains
water consumption data for each class ship. If a particular ship
is not listed in this table, then a similar ship (size, form,
function) should be used as the best available data. Estimated
water consumption is calculated by multiplying the number of days
requirement listed in the ship's characteristics database (SHIPS)
at http://www.efdlant.navfac.navy.mil/LANTOPS_15/home.htm.