| Tweet | 
 
  
    Custom Search
   
 | 
      
         | 
 
       | 
		||
        ![]() MIL-HDBK-1003/13A 
Differential thermostats are available with high temperature protection and 
low temperature (freeze) protection.  High temperature protection is 
important, especially in evacuated tube collectors, in that it prevents a 
very "hot" collector from suddenly receiving a supply of cold water thus 
producing a thermal shock that could damage the collector components. 
Another type of control called proportional control is available.  It is 
similar to the ON/OFF differential controller in operation.  The difference 
is that the proportional controller changes the threshold ON and OFF points 
and controls the flow such that less than full flow can be achieved if the 
sun is at less than full intensity.  The advantage is that the proportional 
control can "turn on" the system when the other controller (the ON/OFF type) 
is waiting for more sun to become available.  This is an advantage on cloudy 
days and early morning start ups.  Overall system efficiency is increased 
slightly with the proportional control.  These controls are more expensive 
and one such experiment at NCEL has shown that proportional controls result 
in considerably more cycling of the pump motor which could shorten pump life. 
It is recommended that the control manufacturer be consulted on this point 
before a proportional control is used. 
As the building requires heat, other controls must direct pumps or blowers to 
provide heat from the storage tank to the load.  This control is the 
conventional thermostat.  The same room thermostat may control the auxiliary 
heater; however, a delay timer or a two-step room thermostat must be 
incorporated into the auxiliary heater control circuit so that the auxiliary 
heat will not come on if heat is available from storage.  Ten minutes has 
been suggested as a typical time delay before auxiliary heat comes on.  Some 
manufacturers supply combination thermostat and solar system controls. 
2.9 Piping, pumps, valves. 
2.9.1 Pipe and header sizing.  Piping should be designed for low pressure 
drop.  All exposed piping should be well insulated with approved weather- 
resistant insulation.  Dielectric unions should be used at connections 
between dissimilar metals.  Rubber or silicone hose used for connections must 
be of a high temperature type.  The pipe ends should have ferrules to provide 
a good seal with the hose.  In low pressure systems, spring type clamps are 
preferred because they compensate for thermal expansion.  Copper pipe is 
preferred to galvanized steel due to its longer life expectancy and relative 
ease of installation.  Thermal expansion should be provided for all piping or 
hard tubing.  Pipe sizing should be in accordance with recognized methods, 
but for most installations the following estimates are reasonable: 
a. 
For a single row of parallel collectors (see Figure 2-6) with "X" 
number of branches, 0.5 gpm flow per collector, water or 50% glycol 
as heat transfer fluid. 
Up to 3 collectors 
- 
1/2-inch headers 
4 to 7 collectors 
- 
3/4-inch headers 
8 to 12 collectors 
- 
1-inch headers 
13 to 18 collectors 
- 
1-1/4-inch headers 
More than 19 collectors 
- 
1-1/2-inch or larger (size for each 
design) 
82 
 | 
			![]()  | 
		|
![]()  | 
		||