Figure D-4. Pleated Cartridge Filters
SPECIFICATIONS
Utilizes 10- to 40-in.cartridge filters.
Flow rate capacities:
6 EFC--up to 60 gpm
12 EFC--up to 120 gpm
18 EFC--up to 180 gpm
24 EFC--up to 240 gpm
1. Vessels are designed to meet or exceed ASME Code, Section X ,and conform to
California Barclays Code.
2. Operating Conditions:
(a) Pressure: 150 psi
(b) Temperature: 150 degrees F
(c) Fluids with a pH of 213
3. Each housing is pressure tested at 300 psi.
4. The vessel barrel is fabricated using Dow Derakane 411-45, a flexible, fatigue
resistant vinylester.
5. All wetted materials meet the requirements of FDA CFR Title 21.
6. Vent connection is standard on all housing.
STANDARD SERIES
6 EFC--10-in. cartridge filter
12 EFC--20-in. cartridge filter
18 EFC--30-in. cartridge filter
24 EFC--40-in. cartridge filter
2 in. NPT Inlet/Outlet
Buna O-ring Seals
Anodized Aluminum/300 ss Series
Externals
D-9